What is an MCCB?

  • MCCB stands for Molded Case Circuit Breaker. It’s an automatic electrical device designed to protect circuits from overloading, short circuits, and current surges.
  • Similar to a miniature circuit breaker (MCB), an MCCB operates like an advanced version of an MCB, offering additional features such as remote closing and adjustable trip settings.
  • MCCBs are commonly used to protect low-voltage distribution systems and are available in ratings up to 2500 Amps and 1.1 kV.

Construction of Molded Case Circuit Breaker:

  1. Frame or Case: The frame surrounds and supports other components while providing insulation. Sealed-case MCCBs cannot be opened except for testing, inspection, and cleaning. Large-frame MCCBs are interchangeable trip circuit breakers, allowing for servicing and maintenance.
  2. Contacts: MCCBs have both fixed and moving contacts responsible for carrying load current. The quality of contact material determines the circuit breaker’s lifetime.
  3. Arc Chute: A set of parallel metal plates (arc chutes) helps extinguish the arc by splitting and lengthening it. These plates are made of ferromagnetic material.
  4. Operating Mechanism: Responsible for opening and closing the current-carrying contacts. It operates based on thermal and magnetic mechanisms.
  5. Terminal Connectors: Used to connect the MCCB to the external circuit.

Functions of MCCBs:

  1. Protection against Overloading:
    • MCCBs monitor the current flowing through a circuit. If the current exceeds the rated value for an extended period (overload), the MCCB trips to prevent damage.
    • The thermal mechanism provides overload protection.
  2. Protection against Short Circuit:
    • In case of a short circuit (e.g., two wires touching), MCCBs rapidly interrupt the fault current.
    • The magnetic mechanism ensures short circuit protection.

Working Principle of MCCB:

  • Thermal Mechanism: Detects gradual overloads. A bimetallic strip heats up due to current flow, causing it to bend and trip the MCCB.
  • Magnetic Mechanism: Detects sudden short circuits. A solenoid coil generates a magnetic field when fault current exceeds a threshold, tripping the MCCB instantly.

Types of MCCBs:

  • Thermal-Magnetic MCCBs: Commonly used for general-purpose protection.
  • Electronic MCCBs: Use digital OCPDs and have higher interrupting ratings.
  • Interchangeable Trip MCCBs: Allow servicing and maintenance.

Type Of Trip Unit:

  • Thermal magnetic Trip Units.
  • Electronic Trip Units.

Thermal magnetic Trip Units (TMF, TMD and TMA):

Thermal magnetic trip units are devices which provide combined protection against overload and short-circuit. This type of trip unit is used for: AC/DC power distribution, electrical equipment protection (transformers, motors, generators) and capacitor protection.

  1. Overload Protection (L):

The protection against overloads is provided by a thermal device with inverse time trip characteristic. Identified by the letter “L”, it is a protection that trips when the fault current exceeds threshold I1 either, adjustable or fixed, according to the type of trip unit.

  • Instantaneous Short Circuit Protection (I):

The protection against short circuit is provided by a magnetic device with a trip time independent of the fault current value. Identified by the letter “I”, it is a protection that trips instantaneously when the fault current exceeds threshold I3 either, adjustable or fixed, according to the type of trip unit.  This protection trips to quickly eliminate high value currents with no intentional delay.

Electronic Trip Units:

Electronic trip units are overcurrent protection based on microprocessor electronics. Compared with Thermal magnetic trip units, they allow precise setting both in terms of current providing more accurate protection.

  1. Overload Protection (L):

Protection against overloads (long time delay trip function, ANSI code 51, AC time overcurrent relay), is identified by Function L. If the fault current exceeds the set threshold I1, this protection trips according to an inverse time characteristic, where the link time-current is represented by the relation I2t = K (constant let-through energy); with this curve, the tripping time decreases as the current increases.

  • Short Circuit Protection with Delayed Trip (S):

Protection against short circuit with time delay trip (short time delay trip function, ANSI code 51, AC time overcurrent relay), is identified by Function S.

  • Instantaneous Short Circuit Protection (I):

The instantaneous protection against short circuit (instantaneous trip function, ANSI code 50, instantaneous overcurrent relay) is identified by Function I.

  • Ground-Fault Protection (G):

The most advanced electronic trip units have an integrated protection against ground faults (ground-fault trip function, ANSI code 51 N, AC time ground fault overcurrent relay) identified with the Function G.

Testing and Maintenance:

  • Regular testing ensures proper functioning.
  • Maintenance includes cleaning, inspection, and replacing worn-out parts.

Advantages of MCCBs:

  • Adjustable trip settings.
  • Remote closing capability.
  • Suitable for low-voltage systems.

Applications:

  • Industrial plants.
  • Commercial buildings.
  • Power distribution networks.